ABB System Pro M Compact S 203 K40 NA Krachtgroep Automaat
Productinformatie
SPECIFICATIONS Additional Information Connecting capacityBusbar 10 / 10 mm²
Flexible with Ferrule 0.75 ... 25 mm²
Flexible 0.75 ... 25 mm²
Rigid 0.75 ... 35 mm²
Stranded 0.75 ... 35 mm² curveK Data sheet, technical information9AKK107991A8329 EclassV11.0 : 27141901 Package level 1 depth / length78 mm Product net depth / length69
mm Rohs statusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 Resistance to vibrations acc5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In Weee category5. Small Equipment (No External Dimension More Than 50 cm) Main product rangeS200 Terminal typeScrew Terminals Number of protected poles3 i²t at switch-on9AKK107992A5103 Mounting typeDIN-Rail degree of protectionIP20
Enclosure with Cover IP40 Complementary Accessories availableYes Actuator markingI / O Ambient air temperatureOperation -25 ... +55 °C
Storage -40 ... +70 °C Cn88536 20 10 Declaration of conformity - ce2CDK403001D0607 Package level 1 gross weight0.51 kg Product net weight0.5
kg [in] rated current40 A Actuator materialInsulation Group II, Black, Sealable Package level 1 height80 mm Product net width70
mm [ics] rated service breaking capacity(230 V AC) 15 kA
(400 V AC) 7.5 kA
(440 V AC) 7.5 kA Country of originGermany (DE) Environmental conditions28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 % Package level 1 unitscarton 1 piece Connecting capacity ul/csaBusbar 18-8 AWG
Conductor 18-4 AWG Package level 1 width92 mm tightening torque2.8 N·m dimension2CDC022007F0010 Package level 2 depth / length395 mm Package level 2 ean4016779974448 Contact position indicationRed ON / Green OFF Environmental information2CDK400030D0201 Package level 2 gross weight11.92 kg Package level 2 height210 mm Idea granular category code (igcc)4897 >> Miniature circuit breakers Operational voltageMaximum (Incl. Tolerance) 440 V AC Package level 2 unitscarton 24 piece Instructions and manuals2CDS207104P0002 mechanical endurance20000 cycle Package level 2 width275 mm Maximum operating voltage ul/csa110 V DC
480Y / 277 V AC Position of neutral terminalsRight Minimum order quantity1 piece Input voltage typeAC/DC Power supply connectionArbitrary wire stripping length12.5 mm Object classification codeF Rated conditional short-circuit current (inc)(230 V) 20 kA
(400 V) 10 kA frequency50 Hz Package level 1 ean4016779610384 Housing materialInsulation Group II, RAL 7035 Offered with extended lifetimeProduct Durability - Achieved Pollution degree3 Product net height88
mm Rated short-circuit capacity(AC) 6 kA
(DC) 6 kA
(400 V AC) 6 kA mounting positionany Rated frequency (f)50 / 60 Hz Rated impulse withstand voltage (uimp)4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV Mounting on din railTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 Rated insulation voltage (ui)acc. to IEC/EN 60664-1 440 V Power loss18 W
at Rated Operating Conditions per Pole 4.5 W Rated operational voltageacc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 440 V AC Reach declaration9AKK107492A1906 Poles description3+N Recommended screw driverPozidriv 2 Resistance to shock acc25g / 2 shocks / 13 ms Tightening torque ul/csa18 in·lb Sustainable material content0 % Rated ultimate short-circuit breaking capacity (icu)(230 V AC) 20 kA
(400 V AC) 10 kA
(440 V AC) 10 kA Environment Built-in depth (t2)69 mm Customs tariff number85362010 Electrical endurance10000 AC cycle Eplan catalog treeElectrical engineering / Protection devices / General Certification agencyEN
IEC
UL Environmental product declaration - epd9AKK108467A7832 Eplan graphical macro9AKK106713A7632 Eplan macro9AKK106713A7622 ETIM - 8EC000042 - Miniature circuit breaker (MCB) overvoltage categoryIII standardsIEC/EN 60898-1
IEC/EN 60947-2
UL 1077 Circular design principles recyclability rateDesign for Closing Resource Loops - Standard EN45555 - 90 % Declaration of conformity - ukca9AKK108467A5053 Etim 7EC000042 - Miniature circuit breaker (MCB) Pole net weight0.125 kg Width in number of modular spacings4 Eplan function definitionNO contact / NO contact, 2 connection points / NO contact, leading 7N_8N
Circuit breaker / Triple circuit breaker / Triple circuit breaker 1_2_3_4_5_6 Scipe6800e55-46b1-49a3-881b-0f66d0e903ad Germany (DE) Weee b2c / b2bBusiness To Business E-number (finland)3210936 Offered with takeback servicesTake Back for Recycling - Achieved Rohs information2CDK403001D0607 Screw terminal typeFailsafe Bi-directional Cylinder-lift Terminal Unspsc39121603 Installation sizeacc. to DIN 43880 1 dielectric test voltage50/60 Hz, 1 min: 2 kV Interrupting rating acc(110 V DC) 10 kA
(277 V AC) 6 kA
(480Y / 277 V AC) 6 kA
Vanaf € 99.95